Opens in a new tab

Daikin FDMRN20AV1KU / RR20AV1KU

Cooling only · R-410A · Concealed ducted split

Daikin FDMRN20AV1KU / RR20AV1KU is a cooling-only R-410A concealed ceiling ducted split. The catalogue lists 5.28 kW (18,000 Btu/h) T1 cooling for the FDMRN20AV1K / RR20AV1K model family.

  • Rated / maximum external static pressure: 40 / 50 Pa
  • Indoor noise H/M/L: 41 / 39 / 36 dB(A)
  • Indoor dimensions: 261 × 1137 × 388 mm (H × W × D)
  • Power supply: 230 V, 1 phase, 50 Hz

AED  4,450.00

Technical Downloads

Daikin FDMRN concealed ceiling units catalogue cover
FDMRN Series
Product catalogue
PDF · 8 pages · 0.4 MB
Daikin FDMRN-A engineering data book cover
FDMRN-A Series
Engineering data book
PDF · 53 pages · 4.4 MB
Daikin FDMRN20 ESMA ECAS certificate preview
FDMRN20
ESMA certificate
PDF · 3 pages · 1176 KB
Valid until 4 March 2027

Daikin FDMRN20AV1KU concealed ceiling ducted split

The FDMRN20AV1KU / RR20AV1KU listing brings ducted cooling to rooms where the indoor equipment is concealed above the ceiling. Its catalogue model family, FDMRN20AV1K / RR20AV1K, provides 18,000 Btu/h of nominal T1 cooling with R-410A refrigerant and a rotary compressor. Air is distributed through a designed duct system to suit the space.

Cooling capacity and efficiency

Store model / outdoor unit FDMRN20AV1KU / RR20AV1KU
Catalogue model family FDMRN20AV1K / RR20AV1K
T1 cooling capacity 5.28 kW / 18,000 Btu/h
T3 cooling capacity 4.62 kW / 15,750 Btu/h
T1 EER 11.91 (Btu/h)/W
T3 EER 8.73 (Btu/h)/W
Power supply 230 V, 1 phase, 50 Hz
Compressor Rotary
Refrigerant / operation R-410A / cooling only

T1 test conditions: indoor 27°C dry bulb / 19°C wet bulb; outdoor 35°C dry bulb / 24°C wet bulb. T3: indoor 29°C dry bulb / 19°C wet bulb; outdoor 46°C dry bulb / 24°C wet bulb. All figures are at 50 Hz. The catalogue uses model-family codes without the store’s trailing U suffix; the figures above are from its standard AV1K/AY1K columns, not the separate RE or K9 variants.

Ductwork, dimensions and installation planning

Rated / maximum ESP at high fan 40 / 50 Pa
Indoor airflow H/M/L 721 / 618 / 432 CFM
Indoor noise H/M/L 41 / 39 / 36 dB(A)
Indoor dimensions H × W × D 261 × 1137 × 388 mm
Outdoor dimensions H × W × D 753 × 855 × 328 mm
Liquid pipe connection 6.35 mm (1/4 inch)
Gas pipe connection 12.7 mm (1/2 inch)
Maximum total / vertical piping 50 m / 30 m
Catalogue operating temperature range 19–54°C

Allow for the 261 mm indoor casing height, service access and the pressure loss of the complete duct system. Use the rated 40 Pa and maximum 50 Pa values when checking the installation design. The operating temperature limit is separate from the rated cooling capacity.

Controls and model-specific features

The series brochure describes Turbo, Sleep and Dry modes and illustrates the BRC51A62Y wired controller. Confirm the controller supplied with your order. Auto random restart resumes operation using the previous settings after a power interruption, with staggered restarting across units.

The FDMRN20–50 family includes the catalogue’s double drain-pan arrangement. The matched outdoor model uses a hydrophilic gold-fin coating on its copper-to-aluminium heat exchanger.

Selecting ducted cooling in Dubai

Match the cooling load, available electrical supply, ceiling space and duct resistance before choosing a system. Compare the Daikin FDMRN range or browse all ducted split air conditioners. Download the original catalogue in Technical Downloads for the full model table, or call Coolwell on 800 26659355 for selection assistance.

Brand

Daikin

Series

FDMRN

T1 Cooling Capacity (Btu/h)

18,000

Daikin FDMRN Ducted Split ImageDaikin FDMRN Ducted Split Concealed ImageDaikin FDMRN Ducted Split Concealed ImageDaikin FDMRN Ducted Split Main Features ImageDaikin FDMRN Ducted Split Technical Specifications Image