Opens in a new tab

Daikin FXMQ250NVE6

8.0 Ton | 28.0 kW | 10 HP | 95,500 Btu/h

Daikin FXMQ250NVE6 is a concealed ducted VRV indoor unit with nominal cooling of 28 kW (95,500 Btu/h) and heating of 31.5 kW.

  • Two airflow settings: 80 / 73 m³/min (high/low).
  • Published external static-pressure settings: 190 / 270 Pa.
  • Indoor body: 440 × 1,490 × 1,090 mm (H × W × D).
  • Single-phase 230 V, 50 Hz supply.

AED  10,200.00

Technical Downloads

Daikin FXMQ-NVE6 ducted technical databook cover
FXMQ-NVE6 Series
Technical data book
PDF · 36 pages · 66.4 MB

Daikin FXMQ250NVE6 concealed ducted VRV indoor unit

The FXMQ250NVE6 is part of the FXMQ-NVE6 ceiling-mounted ducted range. Its 28 kW net cooling and 31.5 kW net heating ratings support selection for larger indoor zones served through a duct network. The unit is concealed above the ceiling, with room air delivered through separately designed ducts and grilles. Match the capacity, fan performance and service clearances to the project requirements.

Cooling and heating specifications

Indoor model FXMQ250NVE6
Net cooling capacity 28 kW / 95,500 Btu/h
Net heating capacity 31.5 kW / 107,000 Btu/h
Manufacturer capacity class 10 HP
Indoor power input, cooling / heating 1.650 / 1.650 kW

Cooling ratings use 27°C dry bulb / 19°C wet bulb indoors and 35°C dry bulb outdoors. Heating ratings use 20°C dry bulb indoors and 7°C dry bulb / 6°C wet bulb outdoors. Both use standard external static pressure, 7.5 m equivalent piping length and zero level difference. Capacities include indoor fan motor heat. Indoor power input is not the electricity consumption of the complete VRV system.

Airflow, duct pressure and acoustics

Airflow, high / low 80 / 73 m³/min
Sound pressure, high / low 49 / 47 dB(A)
Published external static-pressure settings 190 / 270 Pa
Fan Direct-drive sirocco fan
Temperature control Microprocessor thermostat for cooling and heating

Static pressure is selected by changing connectors inside the electrical box, as described in the databook. Check the fan-performance curves against the complete duct resistance; the listed ESP excludes pre-filter pressure drop. Sound levels are anechoic-chamber conversion values measured 1.5 m below the unit centre. Installed sound levels may be higher because of the surrounding conditions.

Dimensions and connections

Indoor body H × W × D 440 × 1,490 × 1,090 mm
Unit mass 130 kg
Electrical supply 1 phase, 230 V, 50 Hz
Liquid pipe 9.5 mm, flare connection
Gas pipe 22.2 mm, brazing connection
Drain pipe 31.5 mm diameter steel pipe
Casing Galvanised steel plate
Refrigerant control Electronic expansion valve

The supplied databook identifies NVE6 as the India-market 230 V, 50 Hz version. Use this exact electrical specification when selecting the unit. Body dimensions do not include the full space required for suspension, duct connections, drainage and service access; refer to the dimensional drawings before installation.

Filter arrangement and system selection

The air-filter specification is listed as optional, and the notes call for a suction-side duct filter with at least 50% dust collection efficiency by the stated gravity method. A pre-filter is also named in the accessories list. Confirm the supplied filter arrangement and include its resistance in the duct design. The databook lists a fuse, over/under-voltage protection and fan-motor thermal protection.

FXMQ-NVE6 technical downloads

Compare the FXMQ-NVE6 range and select the VRV outdoor unit and controls for the complete system. Download the original 36-page engineering databook from Technical Downloads below the purchasing area for specifications, dimensions, electrical information, capacity tables, fan performance and installation guidance.

Brand

Daikin

Series

FXMQ-NVE6

T1 Cooling Capacity (Btu/h)

95,500

T1 Cooling Capacity (HP)

10

T1 Cooling Capacity (kW)

28.0

T1 Cooling Capacity (Ton)

8.0

Daikin FXMQ-NVE6 manufacturer specifications, databook page 5Daikin FXMQ-NVE6 manufacturer specifications, databook page 6